Model FC-BMCS

Single Inlet, Coupling Drive

Performance Characteristics

  • In these systems, the connection of the impeller to the motor is indirectly and coupling.
  • The design of these types of fans is based on the impeller method in the middle of two bearings (Impeller Between Bearing) and also (Impeller Overhung) according to the AMCA standard.
  • The air capacity can reach up to approximately 350,000 cubic meters per hour.
  • The static pressure is up to about 5,000 pascals.
  • The diameter of the fan impeller can reach up to 1600 millimeters.
  • The inlet air volume can be changed with a damper or by changing the speed frequency.
  • These series of fans can have suitable performance in temperatures ranging from -40 to 500 degrees Celsius.
  • The position of the outlet mouth relative to the inlet and its angle relative to the horizon will be selectable according to the AMCA standard.
  • The capability of installing any accessories such as damper, silencer, bird screen, chassis, etc., exists on these air movers.
  • Most of these fans are used in systems for collecting and transferring gases, material transport, and polluted air.
  • Based on the capacity and performance efficiency of the fan, the impeller blades of these fans can be designed as (Backward Curved) or (Backward Inclined).
  • The vibration balance of these fans is according to the ISO standard DIN ISO 1940-1 grade G 6.3 <4 mm/s.

Special Design Methods

  • In environments with high corrosion and acidity, stainless steel 304 or stainless steel 316 materials are used for the body and impeller of fans (stainless-steel Fans).
  • In case of the presence of flammable gases and dust in the environment where the fan is installed, to prevent sparks and explosions, the fan is completely isolated from the surrounding environment, and also a layer of copper or composite insulation is used on the potential collision area of ​​the two-metal impeller and fan body (Explosion & Spark proof Fans).
  • In the oil, gas, and petrochemical industries, centrifugal fans are designed and manufactured according to the international standards API 560 & API 673.