Model FC-FLBD
Single Inlet-Belt Drive
Performance Characteristics
- In these systems, the connection of the impeller to the motor is indirectly and via a pulley-belt mechanism.
- The design of these types of fans is based on the impeller method, both with the impeller between bearings and overhung impeller, according to the AMCA standard.
- The airflow capacity is up to approximately 250,000 cubic meters per hour.
- The static pressure is up to approximately 700 pascals.
- The diameter of the fan impeller reaches up to 1250 millimeters.
- The inlet airflow can be adjusted with a damper or by changing the frequency of the speed.
- These series of fans can perform adequately in temperatures ranging from -40 to 500 degrees Celsius.
- The position of the outlet relative to the inlet and its angle concerning the horizon will be selectable according to the AMCA standard.
- The capability of installing any accessories such as dampers, silencers, bird screens, chassis, etc., on these air movers exists.
- The vibration balance of these fans is according to the ISO standard DIN ISO 1940-1 grade G 6.3 <4 mm/s.
Design Special Methods
- In environments with high corrosion and acidity, stainless steel 304 or stainless steel 316 materials are used for the body and impeller of the fans (stainless-steel Fans).
- In the presence of flammable gases and dust in the fan environment, to prevent sparks and explosions, the fan is fully isolated from the surrounding environment, and also a layer of copper or composite insulation is used on the potential collision area of the two metals, the impeller and the body of the fan (Explosion & Spark proof Fans).
- In the oil, gas, and petrochemical industries, centrifugal fans are designed and manufactured according to the international standards API 560 & API 673.